ORS Corrosion Inhibitor

ORS CORROSION INHIBITOR

This product is a corrosion inhibitor for Open Recirculating Systems or Closed Hot and Chilled Water Systems. Contains no chromate or silicate.

DOSAGE & FEEDING:

  • In closed chilled water system, add 2000 to 3000 ppm. *(2 to 3 gallons per 1000 system gallons)
  • In closed hot water system, add 2000 to 3000 ppm. '(2 to 3 gallons per 1000 system gallons)
  • In open recirculating, add 1000 to 1500 ppm. *(1 to 1.5 gallons per 1000 system gallons)

WARNING:

CORROSIVE MATERIAL: Read Material Safety Data Sheet (MSDS) before using HANDLING PRECAUTIONS: Rubber gloves, safety glasses or goggles, body protection clothing and shoes are required Eye-wash fountains in the workplace are strongly recommended.

EMERGENCY & FIRST AID INSTRUCTIONS: EYE EXPOSURE-Flush immediately with water or normal saline solution for at least 15 minutes Take exposed individual to a health care professional, preferably an opthamologosl, for further evaluation. SKIN EXPOSURE-Wash exposed area with plenty of soap and water. Repeat washing. Remove contaminated clothing and wash thoroughly before reuse. If irritation persists, consult a health care professional
DOT SHIPP G NAME: Corrosive Liquid, NOS (containia Potassium dioxide 8 UN1760
ritation persists, consult a health care professional.

DOT SHIPPING NAME: Corrosive Liquid, NOS (containing Potassium dioxide 8, UNI760 _

INHALATION- Move the exposed individual to fresh air. If the individual is cyanotic or has difficulty breathing, administer Oxygen, if available Treat symptoms. INGESTION DO NOT INDUCE VOMITING. Rinse mouth with copious amounts of water or milk. Irrigate the esophagus and dilute stomach contents by slowly giving one or two glasses of water or milk. Avoid giving alcohol or alcohol related products. In cases where individual is sem comatose, comatose or convulsing. DO NOT GIVE FLUIDS BY MOUTH. In case of intentional ingestion of the product, seek medical attention immediately. Take individual to nearest medical facility.

HARMFUL IF SWALLOWED DO NOT TAKE INTERNALLY KEEP OUT OF REACH OF CHILDREN For Industrial & Insertional Use Only

: